A durable and portable insulation resistance tester designed for both residential and commercial electricians. It conducts insulation tests ranging from 0.01 MΩ to 2000 MΩ, utilizing two test voltages: 500 V and 1000 V. The tester incorporates live circuit detection to safeguard against conducting insulation tests when voltages exceeding 30 V are detected. Additionally, it accurately measures resistance across a range from 0.01 Ω to 20.00 kΩ.
- Call Us +966 50 63 55 182
- Email us : Info@focusgulf.com
- Whatsapp : +966 50 63 55 182
- Shipping Across Saudi Arabia
The Fluke 1503 Insulation Resistance Meter is tailored for essential insulation testing in residential and commercial electrical applications. This compact and robust tool, similar in size to the Fluke 1507 but with fewer features, fits comfortably in hand and offers reliable performance at a competitive price point. It efficiently handles common tests and features a remote probe that streamlines repetitive or difficult-to-access testing tasks. Additional capabilities include:
- Measures AC/DC voltage from 0.1 V to 600 V
- Incorporates auto-discharge of capacitive voltage to enhance user safety
- Provides low-ohms earth-bond continuity (200 mA)
- Features a large, backlit display for clear visibility of results
- Safeguards against overvoltage with CAT IV 600 V rating
- Includes a comprehensive set of accessories: remote probe, test leads, test probes, alligator clips, and a one-year warranty
- Supports hands-free operation with optional Fluke TPAK magnetic hanging system
- Operates on four AA alkaline batteries, delivering enough power for at least 1000 insulation tests before replacement
Specifications: Fluke 1503 Insulation Resistance Meter
AC/DC Voltage Measurement | ||
Accuracy | Range | 600.0 V |
Resolution | 0.1 V | |
50 Hz to 400 Hz ±(% of Rdg + Digits) | ±(2% + 3) | |
Input impedance | 3 MΩ (nominal), < 100 pF | |
Common mode rejection ratio (1 kΩ unbalanced) | > 60 dB at DC, 50 or 60 Hz | |
Overload protection | 600 V rms or DC | |
Earth Bond Resistance Measurement | ||
Range/Resolution | 20.00 Ω | 0.01 Ω |
200.0 Ω | 0.1 Ω | |
2000 Ω | 1.0 Ω | |
20.00 kΩ | 0.01 kΩ | |
Accuracy | ±(1.5% + 3) | |
Overload protection | 2 V rms or DC | |
Open circuit test voltage | > 4.0 V, < 8 V | |
Short circuit current | > 200.0 mA | |
Insulation Specifications | ||
Measurement range | 0.01 MΩ to 2000 MΩ | |
Test voltage | 500 V, 1000 V | |
Test voltage accuracy | + 20%, – 0% | |
Short circuit current | 1 mA nominal | |
Auto discharge | Discharge time < 0.5 second for C = 1 µF or less | |
Live circuit indicator | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 µF load | |
Measure accuracy | ||
500 V | ±(1.5% + 5) | |
1000 V | ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ | |
General Specifications | ||
Maximum voltage applied to any terminal: | 600 V AC rms or DC | |
Storage temperature | -40°C to 60°C (-40°F to 140°F) | |
Operating temperature | -20°C to 55°C (-4°F to 131°F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F) | |
Relative humidity | ||
0% to 95% @ 10°C to 30°C (50°F to 86°F) | ||
0% to 75% @ 30°C to 40°C (86°F to 104°F) | ||
0% to 40% @ 40°C to 55°C (104°F to 131°F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Shock | 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) | |
Electromagnetic compatibility | In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) | |
Safety | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) | |
Certifications | CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition | |
Batteries | Four AA batteries (NEDA 15A or IEC LR6) | |
Battery llife | Insulation test use: | Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
Resistance measurements: | Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
IP rating | IP40 | |
Altitude | Operating | 2000 m CAT IV 600 V, 3000 m CAT III 600 V |
Non-operating (storage) | 12,000 m | |
Over-range capability | 110% of range | |
Included accessories | TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe |